Niko Home Control is evolving into MOTIV Building Control. MOTIV is a new brand for intelligent building automation. Built on the trusted foundation of Niko Home Control, MOTIV solutions are designed to make buildings work more naturally for the people inside them. MOTIV helps professionals create smarter, more comfortable buildings. With technology that works quietly in the background. All existing Niko Home Control solutions remain fully compatible with MOTIV. Over time, the full portfolio will move to the MOTIV brand. During this transition, you will see both Niko Home Control (NHC) and MOTIV Building Control (MBC) appear in this documentation. Discover MOTIV at niko.eu/MOTIV
Hardware Manual
English Danish Dutch French German Slovak Swedish
English Danish Dutch French German Slovak Swedish

LED behaviour on the DALI-2 broadcast module

LED

LED status

Meaning

Proposed action

status LED




LED OFF

The module has been installed and is functioning correctly.


The module has not been connected.

Connect the module.

LED continuous ON

  • The system or module is in TEST mode.

  • The TEST button on the connected controller has been pressed.

Press the TEST button again to leave TEST mode. If the LED doesn’t switch off, contact Niko customer services. The module might be defective.

LED 1/LED 2


LED flashing slowly

(1x per 2 seconds)

LED pattern 0x0001U



DALI bus error (short circuit or no voltage on the bus)

  • Check the BUS wiring.

  • The system might be overloaded, check if the drivers on this channel are within specification (quantity, type and sum of consumption).

  • If the problem persists, contact Niko customer services.

LED flashing rapidly

(8x per 2 seconds)

LED pattern 0x5555U

Communication problem

  • Check the module's power supply.

  • Upgrade the software version using the Niko Home Control programming software.

  • The thermal overheating might be active. Switch off the mains and let the module cool down.

  • The module might be defective.

  • Contact Niko customer services.

LED pulsing

(2x2 per 2 seconds)

LED pattern 0x5050U

Upgrade ongoing

Wait 2 minutes to complete the upgrade.
If the LED doesn’t switch off, contact Niko Customer service.

LED 1/LED 2 + status LED

LED on for 30 sec

One of the buttons has been pressed (all DALI devices on that channel are set ON or OFF).