Niko Home Control is evolving into MOTIV Building Control. MOTIV is a new brand for intelligent building automation. Built on the trusted foundation of Niko Home Control, MOTIV solutions are designed to make buildings work more naturally for the people inside them. MOTIV helps professionals create smarter, more comfortable buildings. With technology that works quietly in the background. All existing Niko Home Control solutions remain fully compatible with MOTIV. Over time, the full portfolio will move to the MOTIV brand. During this transition, you will see both Niko Home Control (NHC) and MOTIV Building Control (MBC) appear in this documentation. Discover MOTIV at niko.eu/MOTIV
Hardware Manual
English Danish Dutch French German Slovak Swedish
English Danish Dutch French German Slovak Swedish

Rail coupler

Description

The rail coupler interconnects the power supply voltage and the bus of the rail below to the modules via the sliding contact.

Overview

https://s3-eu-west-1.amazonaws.com/guideimages/HWScreenshots/V2.0/EN/38-00-001.png

Installation

Follow the steps below to install the rail coupler:

  1. Click the rail coupler at the far left onto the DIN rail.

  2. Connect all four connection terminals (+, –, B1, B2) to the corresponding connection terminals of the connected controller, the rail coupler or the power supply on the previous and next rails.

  3. Each module is fitted with a sliding contact. Slide the sliding contact to the right until it clicks into the next module. This will ensure that the bus and the power supply are connected.

  • Bus cables can be used between terminals B1/B2 of any rail coupler and a control point.

  • A rail coupler can be interconnected to another rail coupler located in a different electrical cabinet. The cable length between both rail couplers should not exceed 20 m. If the distance between the electrical cabinets exceeds 20 m, you must use a new power supply for the second cabinet.

A connected controller, power supply or a rail coupler must be used at the far left of every DIN rail.

Technical data

  • dimensions: DIN 2E

  • sliding contact to connect the module to the following module on the DIN rail

  • 2 x 4 screw terminals for 3 x 1.5 mm² or 2 x 2.5 mm² or 1 x 4 mm²

  • CE marked

  • ambient temperature: 0 - 45°C