Niko Home Control is evolving into MOTIV Building Control. MOTIV is a new brand for intelligent building automation. Built on the trusted foundation of Niko Home Control, MOTIV solutions are designed to make buildings work more naturally for the people inside them. MOTIV helps professionals create smarter, more comfortable buildings. With technology that works quietly in the background. All existing Niko Home Control solutions remain fully compatible with MOTIV. Over time, the full portfolio will move to the MOTIV brand. During this transition, you will see both Niko Home Control (NHC) and MOTIV Building Control (MBC) appear in this documentation. Discover MOTIV at niko.eu/MOTIV
Programming Examples
English Danish Dutch French German Slovak Swedish
English Danish Dutch French German Slovak Swedish

Heating + electrical heating

Use case

Your customer has a combined heating system with 7 zones. Five zones are equipped with a zone valve controlled by a thermostat. Two zones are equipped with electrical heating controlled by a thermostat. A circuit pump is optional.

You can also use push buttons with LED(s) and comfort sensors instead of thermostats, or a combination of both.


Procedure

Creating the controls and the devices
  1. Create the thermostats (THT1 to THT7).

  2. Create the zone valves (VALVE1 to VALVE5).

  3. Create a heating system (H/C1).

  4. Create the electrical heatings (HEAT1 and HEAT2)

  5. (optional) Create a circuit pump (PUMP1).


https://s3-eu-west-1.amazonaws.com/guideimages/Screenshots/V2.9/EN/SPE_005_213_01.png

When there is no circuit pump in the installation, there is no need to configure it in the software.

Creating the routines
  1. Create a routine Heating/cooling per circuit (ROUT1). Use the following behaviour:

    • Select the heating system (H/C1).

    • (optional) Select the circuit pump (PUMP1).

    • Define the heating zones. Combine the correct thermostat with the corresponding zone valve (THT1 and VALVE1, THT2 and VALVE2, ..., THT5 and VALVE5).

    • (optional) Create notifications.

  2. Create a routine Electrical heating (ROUT2). Use the following behaviour, select the electrical heating and corresponding thermostat per zone (HEAT1 and THT6, HEAT2 and THT7).


https://s3-eu-west-1.amazonaws.com/guideimages/Screenshots/V2.9/EN/SPE_005_213_02.png
Filling the cabinet and addressing the devices
  • You can only address four zone valves to a heating or cooling module 4U. Contact 5 of the module is an H/C-contact.

  • Always address the heating system to the first heating or cooling module in the cabinet (contact 5).

Fill the cabinet with ...

and address the following devices ...

a switching module (3x) 2U (MOD1)

the circuit pump PUMP1 (*).

a heating or cooling module 4U (MOD2)

  • the zone valves VALVE1 to VALVE4 (contact 1 to 4 of the module).

  • the heating system H/C1 (contact 5 of the module) (**) (***).

a heating or cooling module 4U (MOD3)

  • the zone valve VALVE5.

  • the electrical heatings (HEAT1 and HEAT2).

(*) You can also address the circuit pump to the H/C contact of another heating or cooling module.

(**) This contact is not physically used in the installation.

(***) The contact closes when one of the thermostats demands heating.


Example

Click here to download the programming example (nhc2 file).


Connection diagram

The figure below shows a connection diagram. In this example, radiators, but also underfloor heating and electrical heating, are used.

https://s3-eu-west-1.amazonaws.com/guideimages/Screenshots/V2.9/EN/SPE_005_213_08.png